HaloSense - Chlorine Analyzer
The HaloSense range of chlorine analyzers are used in many applications requiring the measurement and control of online residual chlorine levels in water. The HaloSenser range is suitable for total or free residual chlorine monitoring or control applications in potable water, seawater, process water, swimming pool water, waste water, food washing, paper and pulp, etc.
The following are available in the HaloSense range of chlorine analyzers:
- Online total chlorine analyzer 0-2 ppm, 0-5 ppm, 0-10 ppm, 0-20 ppm, 0-200 ppm
- Online free chlorine analyzer 0-2 ppm, 0-5 ppm, 0-10 ppm, 0-20 ppm, 0-200 ppm
- Online residual chlorine in seawater analyzers (free or total bromine) 0-2 ppm, 0-5 ppm, 0-10 ppm, 0-20 ppm
- Online zero free chlorine analyzer (designed to measure the absence of free chlorine) 0-2 ppm, 0-5 ppm, 0-10 ppm for applications such as post activated carbon and pre-RO monitoring.
Specification
Chlorine Sensor Probe
Type: Membrane covered potentiostatic chrono amperometric three-electrode system
Measurand: Total Chlorine or Free Chlorine
Range: 0.01-2, 0.01-5, 0.01-10mg/l, 0.01-20mg/l, 0-200mg/l (ppm)
Resolution: 0.01mg/l (ppm)
Reproducibility: ±5 %
Stability: -2 % per month (without calibration)
Working electrode: Gold
Counter electrode: Stainless Steel
Reference electrode: Silver / silver halide
Membrane material: Micro-porous hydrophilic membrane
Flow rate: Approximately 0.5l/min (min 0.2l/min)
Temperature range: >3 to <50 oC
Temperature compensation: Automatically by an integrated thermistor
pHrange: pH 4 up to pH 9
Response time: T90: approx.120 seconds
Calibration: Manual using DPD
Housing material: PVC, silicone, polycarbonate stainless steel
Maintenance intervals:
Membrane: 12-18 months
Electrolyte: 3-6 months
Interferences: High levels of other oxidants such as Ozone and Chlorine Dioxide